MIL-PRF-62439B(AT)
3.4 Performance. Assemblies shall meet the following performance requirements listed
below as 3.4.1 through 3.4.11 with their respective tolerances listed in table I. Performance
operation shall require diesel fuel conforming to No. 2-D of A-A-52557.
TABLE I. Tolerances.
20 °F
150 °F
85 °F
Function
.856 sp. gr. 1/
.800 sp. gr.
.830 sp. gr.
Minimum Wf *2/
43±5 pph
40±5 pph
42±5 pph
0.60 volts req *
61±6 pph
58±6 pph
60±5 pph
1.50 volts req *
150±12 pph
142±12 pph
147±11 pph
2.00 volts req *
199±13 pph
189±13 pph
195±12 pph
4.00 volts req *
411±25 pph
390±25 pph
403±17 pph
7.00 volts req *
714±28 pph
679±28 pph
700±19 pph
Maximum Wf *
814±30 pph
775±30 pph
799±21 pph
Back-up Wf *
128±11 pph
121±11 pph
125±0 pph
Relief valve
1125±60 psig
1125±60 psig
1125±45 psig
7.0 cm3/m max
7.0 cm3/m max
5.0 cm3/m max
Cut-off valve leak
PTS F/B @ 5.140"
-6.50±0.10 volts
-6.50±0.10 volts
-6.50±0.05 volts
IGV F/B @ 5.470"
-0.67±0.15 volts
-0.67±0.15 volts
-0.67±0.08 volts
PTS actuator 9 ma
20 - 160 psid 3/
20 - 160 psid
30 - 150 psid
PTS actuator 900 ma
20 - 160 psid
20 - 160 psid
30 - 150 psid
IGV actuator 0 ma
20 - 85 psid
20 - 85 psid
30 - 75 psid
IGV actuator 900 ma
20 - 85 psid
20 - 85 psid
30 - 75 psid
Pressure test
1100 psig
1100 psig
1100 psig
1/ Sp. gr. = specific gravity
2/ Wf = fuel flow
3/ PSID = pounds per square inch differential
* = metering valve position
1.0 volt = 100 pph reference fuel @ 60 °F
NOTES:
(1) Reference fuel @ 20 °F is 12 centistokes
(2) Tolerance at 20 °F fluid temperature applies at fuel handling unit (fhu) ambient
@ -70 °F.
3.4.1 Minimum fuel flow. The assembly shall provide a fuel flow of no less than
42±2 pounds per hour (pph) (see 4.5.3.1).
3.4.2 Backup valve operation. The assembly shall supply a fuel flow of 118±6 pph with
loss of electrical power to the assembly (see 4.5.3.2).